© Viessmann 5443203
| 6
SCU224
S1
S2
S4 / TR
System layout 1
The controller calculates the temperature difference bet-
ween collector sensor S1 and tank sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference (DT O), the solar pump will be
operated by relay 1, and the tank will be loaded until the
switch-off temperature difference (DT F) or the maximum
tank temperature (S MX) is reached.
Sensors S3 and S4 can optionally be connected for mea-
surement purposes.
R1
Arr 1
S3
1.4 Terminal allocation in the different system layouts
Display Channels
Channel Description Terminal Page
INIT
x*
ODB initialization active - 37
FLL
x*
ODB filling time active - 37
STAB
x*
ODB stabilization in progress - 37
COL x Temperature collector S1 37
TST x Temperature tank S2 37
S3 x Temperature sensor 3 S3 37
S4 x Temperature sensor 4 S4 37
TR x* Temperature return sensor S4 37
n % x Pump speed R1 R1 38
hP x Operating hours R1 R1 38
hP1 x* Operating hours R1 (if OBST is activated) R1 38
hP2 x* Operating hours R2 (if OBST is activated) R2 38
kWh x* Heat quantity kWh - 38
MWh x* Heat quantity MWh - 38
TIME x Time - 34
If energy metering (OHQM) is activated, sensor S4 has to
be connected as return sensor.
If the drainback option (ODB) is activated, relay 2 can be
used to operate a booster pump by activating the booster
function (OBST).
Note:
Viessmann Vitosol collectors cannot be used in
drainback systems.