21 |
SCU224
Legend:
Symbol Specification
x Channel is available
x* Channel is available if the corresponding option is activated.
Adjustment Channels
Channel Description Factory setting Page
Arr x System 6 39
DT1O x Switch-on temperature difference 1 12.0 °Ra [6.0 K] 39
DT1F x Switch-off temperature difference 1 8.0 °Ra [4.0 K] 39
DT1S x Nominal temperature difference 1 20.0 °Ra [10.0 K] 39
RIS1 x Rise control R1 4 °Ra [2 K] 39
n1MN x Minimum pump speed R1 30 % 39
S1 MX x Maximum temperature tank 1 140 °F [60 °C] 40
DT2O x Switch-on temperature difference 2 12.0 °Ra [6.0 K] 39
DT2F x Switch-off temperature difference 2 8.0 °Ra [4.0 K] 39
DT2S x Nominal temperature difference 2 20.0 °Ra [10.0 K] 39
RIS2 x Rise control R2 4 °Ra [2 K] 39
n2MN x Minimum pump speed R2 30 % 39
S2MX x Maximum temperature tank 2 140 °F [60 °C] 40
EM x Emergency temperature collector 270 °F [130 °C] 40
OCC x Option collector cooling
OFF 41
CMX x* Maximum collector temperature
230 °F [110 °C] 41
OSYC x Option system cooling OFF 41
DTCO x* Cooling switch-on temperature difference
40.0 °Ra [20.0 K]
41
DTCF x* Cooling switch-off temperature difference
30.0 °Ra [15.0 K]
41
OSTC x Option tank cooling OFF 42
OHOL x* Option holiday cooling OFF 42
THOL x* Holiday cooling temperature 110 °F [40 °C] 42
OCN x Option minimum limitation OFF 42
CMN x* Minimum collector temperature 50 °F [10 °C] 42
OCF x Option antifreeze OFF 42
CFR x* Antifreeze temperature 40.0 °F [4.0 °C] 42
PRIO x Priority 1 43
tLB x Break time 2 min 43
tRUN x Circulation runtime 15 min 43
DTSE x* Spread temperature difference 70 °Ra [40 K] 43
O TC x Option tube collector OFF 44
TCST x* OTC starting time 07:00 44
TCEN x* OTC ending time 19:00 44
TCRU x* OTC runtime 30 s 44
TCIN x* OTC standstill interval 30 min 44
MAN1 x Manual operation R1 Auto 46
MAN2 x Manual operation R2 Auto 46
LANG x Language En 46
UNIT x Temperature unit °C 46
RESE x Reset - back to factory defaults 46
W0050100 Version number