5. Tips for fault indication
If a malfunction occurs, it will be indicated on the display of
the controller:
Operating control lamp
Warning symbol
12
S1 S2 S3
3456
Temp. Sensor Pt1000
LNR1NR2N
201918171615
S4
78
141312
DE - 45527 Hattingen
DeltaSol BS Plus
2 (1) A 115
2
V~
(1) A 115V~
R1
R2
T4A
115 V~
CU 72060171 01
UL 60730-1A:2002
CSA E60730.1:2002
VBus
910
can fuse 4A
Operating control lamp offOperating control lamp ashes red. On the display the
symbols and appear.
°F Ω °F Ω
14 961 131 1213
23 980 140 1232
32 1000 149 1252
41 1019 158 1271
50 1039 167 1290
59 1058 176 1309
68 1078 185 1328
77 1097 194 1347
86 1117 203 1366
95 1136 212 1385
104 1155 221 1404
113 1175 230 1423
122 1194 239 1442
Resistance values of the
Pt1000-sensors
Check the power supply
o.k.
The can fuse of the controller is defective.
It can be replaced after removal of the
front cover (spare fuse is enclosed in the
accessory bag).
Sensor defect. An error code is shown
on the relevant sensor indication channel
instead of a temperature.
- 88.8888.8
Line break. Check
the line.
Short-circuit.
Check the line.
Pt1000-temperature sen sors can be che-
cked with an ohmmeter. The following
table lists the corresponding resistance
values for different temperatures.
Przeglądanie stron 20