Read and save these instructions
for future reference.
Please file in Service Binder
Product may not be exactly as shown
5693 973 - 05 02/2015
for use by heating contractor
VITOTRONIC 300, GW5B
VITOTRONIC 300-K, MW1B
Installation and Service
Instructions
Vitotronic 300-K, MW1B
Vitotronic 300, GW5B
Vitotronic 300, Type GW5B
Digital boiler control unit
Vitotronic 300-K, Type MW1B
Weather-compensated digital cascade control unit
IMPORTANT
Certified as a component
part for Viessmann boilers
Przeglądanie stron 0
1 2 3 4 5 6 ... 115 116

Podsumowanie treści

Strona 1 - Instructions

Read and save these instructionsfor future reference.Please file in Service BinderProduct may not be exactly as shown5693 973 - 05 02/2015for use b

Strona 2 - Product Information

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0510Preparing for InstallationSystem Example (continued)Equipment requiredPos. Des

Strona 3 - Table of Contents

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05100“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continue

Strona 4

1015693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continue

Strona 5

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05102“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continue

Strona 6 - About these Instructions

1035693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connection and Wiring DiagramWiring, Vitotronic 300, GW5BA1 PCB, extension

Strona 7 - Safety Terminology

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05104Connection and Wiring Diagram (continued)Main PCB low voltageLegend! Outdoo

Strona 8 - Overview of System Example

1055693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connection and Wiring Diagram (continued)Wiring, Vitotronic 300, GW5BF1, F2

Strona 9 - System Example

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05106Connection and Wiring DiagramOverviewWiring, Vitotronic 300-KLegendA1 PCB,

Strona 10 - System Example (continued)

1075693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connection and Wiring Diagram (continued)PCB 120V~Wiring, Vitotronic 300-KLeg

Strona 11

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05108Connection and Wiring Diagram (continued)Wiring, Vitotronic 300-KPCB low volt

Strona 12

1095693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connection and Wiring Diagram (continued)Wiring, Vitotronic 300-KLegend? Su

Strona 13

115693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Preparing for InstallationSystem Example (continued)Equipment requiredPos. Des

Strona 14

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05110ComponentsNote: H The supply temperature sensor can be used as a contact or i

Strona 15

1115693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Boiler Coding CardBoiler Boiler coding cardDisplay in brief scan Part no.Vito

Strona 16 - (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05112Components Extension EA1 Accessory (optional)The DHW recirculation pump is st

Strona 17

1135693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Parts List Vitotronic 300, GW5BParts ListsOrdering Replacement Parts: Please

Strona 18

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05114Parts List Vitotronic 300-K0037 Emissions test switch, single-pole0038 ON

Strona 19 - 120V External Connection

1155693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Specification Vitotronic 300, GW5BSpecificationRated relay output breaking ca

Strona 20

Technical information subject to change without notice. Printed on environmentally friendly (recycled and recyclable) paper.5693

Strona 21 - Connecting Actuators

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0512Preparing for InstallationSystem Example (continued)Electrical installation wi

Strona 22

135693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Preparing for InstallationSystem Example (continued)

Strona 23 - Connections to Terminal aBA

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0514System Example (continued)Preparing for InstallationCode required at every Vit

Strona 24

155693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Overview of Electrical ConnectionsInstallation, Vitotronic 300, GW5BNote: Whe

Strona 25 - IMPORTANT

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0516 Overview of Electrical Connections (continued)Installation, Vitotronic 300, G

Strona 26

175693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Installation, Vitotronic 300, GW5B 120V External Connection OverviewPumps 120V

Strona 27 - B Din rail

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0518Inserting Cables and Applying Strain ReliefLegendA Cables with moulded strain

Strona 28 - Mounting the Control Unit

195693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connecting SensorsLegendMain PCB low voltageaJA Return temperature sensor T1

Strona 29

5693 973 - 05Vitotronic 300, GW5B and MW1B Installation and Service GeneralSafety, Installation and Warranty RequirementsPlease ensure that these ins

Strona 30 - Connecting Pumps

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0520 120V External Connection (continued)120V pumps with an amperage draw of >2

Strona 31

215693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connecting ActuatorsInstallation, Vitotronic 300, GW5BAvailable connectionsgS

Strona 32

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0522Installation, Vitotronic 300, GW5BConnecting the Central Fault Message Facilit

Strona 33 - Connecting Actuators

235693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Installation, Vitotronic 300, GW5B Connections to Terminal aBA WARNINGThe term

Strona 34

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0524Installation, Vitotronic 300, GW5BBlocking Boiler Externally/Adding to the Boi

Strona 35

255693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connecting the BurnerInstallation, Vitotronic 300, GW5BThe burner cables are i

Strona 36

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0526Overview of Electrical ConnectionsNote: When connecting plugs aVD, aVH, sA, s

Strona 37 - Making the LON Connection

275693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Overview of Electrical Connections, Vitotronic 300-K (continued)LegendA Vitotr

Strona 38 - Power Supply

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0528Mounting the Control Unit1. Fasten metal backplate onto mounting surface with

Strona 39 - Opening the Control Unit

295693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Installation, Vitotronic 300-KLegendA Cables with moulded strain reliefB On-si

Strona 40 - Commissioning

Page5693 973 - 053Table of ContentsVitotronic 300, GW5B and MW1B Installation and Service GeneralSafetyPreparing for InstallationInstallation, Vitot

Strona 41

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0530Connecting PumpsPumps 120VRated current: 2 A~* Maximum pump output 6FLA shar

Strona 42

315693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Installation, Vitotronic 300-KInstallation point for outside temperature senso

Strona 43

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0532120V pumps with an amperage draw of >2FLA208/460/575V 3 phase pumps 240V pu

Strona 44

335693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connecting ActuatorsAvailable connectionsgS A1 Motor for 3-way mixing valve,

Strona 45

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0534Installation, Vitotronic 300-KExternal Demand Via Switching ContactConnection

Strona 46

355693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service External Demand via 0–10V InputConnection at input 0 – 10V at extension EA1 (s

Strona 47

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0536External “Mixing Valve Closed”/”Mixing Valve Open” Connection options: H Plug

Strona 48 - Adjusting Heating Curves

375693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Making the LON ConnectionThe Viessmann LON system is designed for the “Line” B

Strona 49

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0538Power SupplyPower SupplyWARNINGThe control must be grounded.Ensure that “L”, “

Strona 50 - Exiting the Service Menu

395693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Fitting the Control Unit FrontOpening and Closing the Control UnitsOpening the

Strona 51 - Calling up the Service Menu

Table of Contents4 Page5693 973 - 05Vitotronic 300, GW5B and MW1B Installation and Service Power SupplyOpening and Closing the Control UnitsCommission

Strona 52 - Brief Scan

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0540Testing the High Limit Safety Cut-out1. Hold down the “TEST” key until the bu

Strona 53 - Fault Codes

415693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Matching the Coding Addresses to the System VersionCheck the following coding

Strona 54 - Fault Codes (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0542Commissioning1. Press .2. “Boiler sequence”3. Select the required boiler seq

Strona 55 - Fault Display

435693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service CommissioningConnecting the Control Unit to the LON H The LON communication mo

Strona 56

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0544Connecting the Control Unit to the LON (continued)CommissioningABCDEMulti boil

Strona 57

455693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Connecting the Control Unit to the LON (continued)Carrying out a LON participa

Strona 58

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0546Commissioning Checking Actuators and Sensors at the Vitotronic 300 GW5BTesting

Strona 59

475693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Checking Actuators and Sensors at the Vitotronic 300-KCommissioningThe followi

Strona 60 - Function Description

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0548Settings in the factory set condition: H Slope = 1.4 H Shift = 0The heating cu

Strona 61

495693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Adjusting Heating Curves (continued)Reduced set room temperatureChanging the r

Strona 62

Table of Contents5 Page5693 973 - 05Vitotronic 300, GW5B and MW1B Installation and Service Code 1, Vitotronic 300, GW5BCode 2, Vitotronic 300, GW5BCo

Strona 63

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0550Service Scans, Vitotronic 300, GW5B Calling up the Service MenuPress OK and

Strona 64

515693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Calling up operating data1. Press OK and simultaneously for approx. 4 sec.2

Strona 65

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 05521. Press OK and simultaneously for approx. 4 sec.2. “Diagnosis”3. “Brief sc

Strona 66

535693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Fault CodesTroubleshooting, Vitotronic 300, GW5BDisplayed fault codeSystem cha

Strona 67

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0554Fault Codes (continued)Troubleshooting, Vitotronic 300, GW5BDisplayed fault co

Strona 68

555693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Fault DisplayCalling up acknowledged fault messagesExtended menu:1. 2. “Fault”

Strona 69

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0556Fault CodesTroubleshooting, Vitotronic 300-KDisplayed fault codeSystem charact

Strona 70

575693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Fault Codes (continued)Troubleshooting, Vitotronic 300-KDisplayed fault codeSy

Strona 71 - Group 1 “General”

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0558Fault Codes (continued)Troubleshooting, Vitotronic 300-KDisplayed fault codeSy

Strona 72 - Group 2 “Boiler”

595693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Fault Codes (continued)Troubleshooting, Vitotronic 300-KDisplayed fault codeSy

Strona 73 - Calling up Coding Level 2

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 056SafetyAbout these InstructionsTake note of all symbols and notations intended t

Strona 74 - Group 1 “General” (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0560Boiler Temperature Control of the Vitotronic 300 GW5BFunctionsThe boiler water

Strona 75

615693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Boiler Temperature Control of the Vitotronic 300, GW5B (continued)Permanent sw

Strona 76

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0562Cascade Control of the Vitotronic 300-KCascading LayoutsBoilers connected in p

Strona 77

635693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Cascade Control of the Vitotronic 300-K (continued)Function DescriptionConvent

Strona 78 - Group 2 “Boiler” (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0564Cascade Control of the Vitotronic 300-K (continued)Conventional strategy 1 (co

Strona 79

655693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Brief description H The control unit has control circuits for one system circu

Strona 80 - “General” Group

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0566Heating Circuit Control Unit of the Vitotronic 300-K (continued)Extended econo

Strona 81 - “DHW” Group

675693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Heating Circuit Control Unit of the Vitotronic 300-K (continued)Differential t

Strona 82 - “Solar” Group

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0568Heating Circuit Control Unit of the Vitotronic 300-K (continued)Control sequen

Strona 83 - Coding 1, Vitotronic 300-K

695693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service DHW Tank Temperature Control of the Vitotronic 300-KFunctionsTime programAn au

Strona 84

75693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service If you smell gasH Don’t smoke! Don’t use naked flames or cause sparks (e.g.

Strona 85

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0570DHW Tank Temperature Control of the Vitotronic 300-K (continued)Function Descr

Strona 86

715693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Calling up Coding Level 1Coding 1, Vitotronic 300, GW5BGroup 1 “General”Coding

Strona 87

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0572Coding 1, Vitotronic 300, GW5BCodingCoding in the factory set condition Possib

Strona 88 - “General” Group (continued)

735693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Calling up Coding Level 2Coding 2, Vitotronic 300, GW5BNote: At coding level 2

Strona 89

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0574Group 1 “General” (continued)Coding 2, Vitotronic 300, GW5BCodingCoding in the

Strona 90

755693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Group 1 “General” (continued)Coding 2, Vitotronic 300, GW5BCodingCoding in the

Strona 91

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0576Coding 2, Vitotronic 300, GW5BGroup 1 “General” (continued)Coding in the facto

Strona 92

775693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Group 1 “General” (continued)Coding 2, Vitotronic 300, GW5BCoding in the facto

Strona 93 - “Cascade” Group (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0578Group 2 “Boiler” (continued)Coding 2, Vitotronic 300, GW5BCoding in the factor

Strona 94 - “DHW” Group (continued)

795693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Calling up Coding Level 11. Press OK and simultaneously for approx. 4 sec.2

Strona 95

85693 973 - 05Vitotronic 300, GW5B and MW1B Installation and Service Preparing for InstallationDesignations in the System ExampleOverview of System E

Strona 96 - “Solar” Group (continued)

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0580“General” GroupCoding 1, Vitotronic 300-KCodingCoding in the factory set condi

Strona 97

815693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Cascade” GroupCoding 1, Vitotronic 300-KCodingCoding in the factory set condi

Strona 98

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0582“Solar” GroupCoding 1, Vitotronic 300-KOnly in conjunction with solar control

Strona 99

835693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” GroupCoding 1, V

Strona 100 - Coding 2, Vitotronic 300-K

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0584“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continued

Strona 101

855693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continued

Strona 102

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0586Calling up Coding Level 21. Press OK and simultaneously for approx. 4 sec.2

Strona 103 - Connection and Wiring Diagram

875693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service CodingCoding in the factory set condition Possible change00:1 One system circu

Strona 104 - Wiring, Vitotronic 300, GW5B

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0588“General” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set

Strona 105

895693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “General” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set

Strona 106

95693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service Preparing for InstallationSystem Example Multi boiler system: Vitocrossal 200 C

Strona 107 - Wiring, Vitotronic 300-K

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0590“General” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set

Strona 108

915693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “General” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set

Strona 109

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0592“Cascade” GroupCoding 2, Vitotronic 300-KCodingCoding in the factory set condi

Strona 110 - Components

935693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Cascade” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set

Strona 111 - Mixing Valve Motor Kit

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0594“DHW” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set con

Strona 112

955693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Solar” GroupCoding 2, Vitotronic 300-KCodingCoding in the factory set conditi

Strona 113 - Parts Lists

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0596“Solar” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set c

Strona 114 - Parts List Vitotronic 300-K

975693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Solar” Group (continued)Coding 2, Vitotronic 300-KCoding in the factory set c

Strona 115 - Specification

Vitotronic 300, GW5B & MW1B Installation and Service 5693 973 - 0598“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” GroupCoding 2, V

Strona 116 - 5693 973 - 05

995693 973 - 05Vitotronic 300, GW5B & MW1B Installation and Service “Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group (continued